Capacitor with fuse and contactor CAB

CAB series are formed by connecting a POLB or FML three-phase power factor correction capacitor to HRC fuses, contactor, fast discharge resistors and limiting inductances. Control can be done by an external signal through a terminal block or by an on/off switch included in the equipment.

These capacitors are specially designed for the individual compensation of transformers, hoisting motors equipments and motors with star/delta starter or electromagnetic brake.

Accessories: Automatic controller

Rated voltage230 … 440 V
Frequency 50 Hz – 60 Hz
Capacitor (Type 1)POLB (only enclosure)
Capacitor (Type 0)FML
Discharge resistorsFitted
Max. overvoltage1.1 Un
Max. overcurrent1.3 In
Insulation level3 kV rms / 15 kV cresta
Temperature range– 40/ +55ºC
Terminals M10
ColourRAL 7035
Standards of fusesIEC 269, IEC 60269-1
Standards IEC 60831, EN 60831

Other powers, voltages and frequencies on request.