Project Description

High pass filter HPF

HPF filters are specially designed to remove harmonics from the current absorbed by 6 pulse power converters, such as frequency converters for motors, UPS, welding equipment, etc. They are essentially passive filters based on a series-parallel combination of inductance and capacitors. (Main function is to filter the 5th and 7th current harmonic and to decrease the level of the 11th and 13th current harmonics). With these HPF filters we will be able to get a reduction of the THD (I) level higher than a simple input reactor reduction, decreasing THD (I) to values below 8%. At full load conditions the THD (I) becomes lower than 5%.

Accessories:

  • Overcorrection regulating Kit
  • Measuring kit
Rated voltage400 ~ 480 V
Frequency50/60 Hz
RMS load current (Ic)4 … 1000 A
Max. overload1 min. a 1,5 Ic
Filtered RMS current (If)1.6 … 72 A
THD residual currentAprox. 8%
Voltage drop at In< 2%
ConstructionMetal cabinet
Protection degreeIP20
ColourGrey RAL 7035
InstallationIndoor
AssemblyA/B type: Wall mounting, C/D type: Floor mounting
StandardsEN 60439, EN 60831, UNE-EN 61000-6-3,UNE-EN 61000-6-4

Other powers, voltages and frequencies on request.

FileLanguageDateSize
Datasheet11/09/20190.2 MB

Contact us if you need more information